A pump doesn't have a flow rate of its own — it delivers whatever the pipe and its fittings allow, and this chapter builds that number from bore to NPSH margin before the drawing leaves the office.
Pipe sizing starts from a required flow, not from a pipe you happen to have on the shelf. Once you know the volumetric flow Q the system must move, the diameter you choose sets the mean velocity: for a fixed Q, a narrower bore means a faster stream, a wider bore a slower one. The area–velocity relationship looks trivial, but the choice of design velocity is where the real judgement sits, because friction loss, erosion, noise and cost all swing on it.
Marine piping guides settle on velocity bands rather than a single number: suction lines are kept slow, typically 1 to 2 m/s, because a fast, turbulent stream arriving at the pump inlet strips away the margin of available suction head before the fluid has even reached the impeller eye. Discharge lines can run faster, commonly 2 to 3 m/s, because the pump is pushing rather than pulling and a little extra velocity head is cheap once the fluid is already pressurised. Seawater and other erosive duties tighten this further: at sustained high velocity the protective film on the pipe wall wears away faster than it can re-form, and metal loss accelerates at bends, branches and anywhere the flow separates from the wall — erosion-corrosion, a materials problem caused entirely by a hydraulic choice.
Compute the minimum bore for the upper velocity limit, then round up to the next standard pipe size — never down — and check the resulting actual velocity leaves margin for the bore fouling over the ship's life.
Once the bore is fixed, the pipe resists the flow with a pressure drop that Darcy and Weisbach's equation ties directly to velocity, length and diameter.
The friction factor f is not a fixed material property; it depends on the Reynolds number Re = VD/ν and on the pipe's relative roughness (wall roughness height divided by bore), and its value is read from the Moody chart, or an equivalent correlation, once both are known. Two regimes behave very differently. Below roughly Re = 2000 the flow is laminar — it moves in smooth, orderly layers, viscosity dominates, and the friction factor collapses to a simple closed form, f = 64/Re, falling as flow increases. Above roughly Re = 4000 the flow is turbulent — eddies mix the fluid across the pipe, wall roughness starts to matter, and f settles onto a Moody-chart curve that depends on both Re and relative roughness. Marine piping runs are almost always turbulent in normal service; the laminar formula mostly matters for viscous duties such as cold lubricating oil.
The velocity-squared term is the one to remember above all the others: double the flow through a fixed bore and the friction loss does not double, it quadruples. That single fact is why velocity limits, not just capacity limits, drive the sizing decision.
Straight pipe is rarely the whole story. Every strainer, bend, tee, reducer and valve disturbs the flow and dissipates energy as the stream separates and re-mixes downstream of the fitting, and this is accounted for as a minor loss.
The word "minor" is worth treating with suspicion. A long, unobstructed transit main really can be dominated by its straight-pipe friction, but a short engine-room run packed with a suction strainer, two or three bends around machinery, a non-return valve and an isolating valve can lose more head in its fittings than in all its straight pipe combined — exactly the situation a designer who only checks the straight-pipe Darcy–Weisbach term will miss. The practical fix is to convert every fitting's K factor into an equivalent length of straight pipe that would give the same loss, add that to the physical pipe length, and run the friction calculation once against the total, so nothing is left uncounted.
Valve choice matters here too: a full-bore gate or ball valve, wide open, contributes very little resistance, while a globe valve, whose flow path turns through the body even fully open, carries a meaningfully higher K in its best-case position. Where a valve is also used for throttling, its K factor at partial opening — not its wide-open value — is the one that belongs in the calculation for that duty.
A pump raises the fluid's pressure, and where the layout calls for it, its elevation, against everything the piping resists. The hydraulic power it delivers to the fluid, and the shaft power its driver must supply to produce that, are related through the pump's efficiency.
The system curve is the piping's own signature: the total head it demands as a function of flow, made up of a static term — whatever elevation and pressure difference exists whether or not fluid is moving — plus a friction term that grows with the square of flow, since velocity itself is proportional to flow for a fixed bore. Plotted against flow this is a rising parabola, offset upward by the static term, or passing straight through the origin where there is none, as in a closed cooling loop. The pump curve runs the opposite way: head falls as flow rises, because forcing more flow through a given impeller at a given speed costs pressure.
Neither curve alone tells you what the system will do. A pump does not have a flow rate any more than a system does; the point where the two curves cross, the duty point, is the only flow and head the installed combination can produce, and every other check in this chapter is made at that point, not at a flow taken off the data sheet in isolation.
Net positive suction head is the margin, expressed as head, between the pressure at the pump's suction and the fluid's vapour pressure at that temperature — the cushion that keeps the liquid from flashing to vapour as it accelerates into the low-pressure eye of the impeller. If that margin runs out, vapour bubbles form and then collapse violently as they reach a higher-pressure region inside the pump; the resulting cavitation erodes the impeller, drops performance sharply, and is audible as a rattling or gravel-like noise.
NPSH available describes what the installation offers, built up from the source: atmospheric or tank pressure converted to head, plus or minus the static height between the source surface and the pump centreline, less the suction-line friction, less the vapour pressure converted to head. The sign on the static term is the detail that decides the whole calculation — with a flooded suction the source sits above the pump and that head helps, so it is added; with a suction lift the pump has to pull the fluid up to itself and that same head works against it, so it is subtracted. Treating a lift as a flooded suction overstates NPSH available by twice the lift distance, enough to turn a genuinely marginal installation into one that looks safe on paper.
NPSH required is a property of the pump itself at a given flow, taken from the manufacturer's curve, and the installation is only sound once the available figure exceeds it by a margin — commonly at least 0.5 to 1 m, more for hot or volatile duties — never merely equal to it.
When a centrifugal pump's running speed changes and its impeller geometry does not, three simple ratios link the old and new operating points.
The cube law on power has the practical payoff: slow a pump to 80 percent of its speed and it draws only about half its former power, which is the economic case for variable-speed drives on part-load duties like closed cooling-water circuits, where the system curve has no static term and the true duty point at reduced speed lies exactly on the path these ratios predict.
The same three ratios are sometimes reached for when an impeller is trimmed to a smaller diameter at constant speed instead of the speed being changed, and this is where marks are lost: the diameter-trim relationships are only an approximation, reasonable over small trims and increasingly unreliable as the cut gets larger, because trimming changes the impeller's internal flow geometry in a way a pure speed change does not. A trimmed-impeller duty point should be checked against the manufacturer's trimmed-diameter curve, not assumed from the speed-change ratios.
Specific speed groups pumps of very different physical size but the same hydraulic character, and its value at the duty point points toward whether a radial, mixed-flow or axial-flow impeller is the right family for the job, well before any single pump's curve is opened.
The three examples below carry a piping design through from a bare flow requirement to a checked, working system: sizing a main and totalling its losses, proving the suction side against cavitation, and re-rating a pump by speed rather than by guesswork.
A centrifugal pump has to deliver 360 m³/h (0.100 m³/s) of seawater through a discharge main between the pump and the deck header. Design practice for this seawater duty caps the discharge velocity at 2.5 m/s. The nearest standard pipe above the calculated minimum bore is DN250, actual bore 260 mm. The run is 45 m of straight pipe, and its strainer, bends and valves have a combined equivalent length of 15 m. Kinematic viscosity of seawater is 1.05×10⁻⁶ m²/s, and the Moody chart gives a Darcy friction factor of 0.020 for this pipe's relative roughness at the resulting Reynolds number. Find the actual working velocity and the total friction head over the run.
Q = 0.100 m³/s (360 m³/h) Design velocity limit, discharge = 2.5 m/s Selected pipe: DN250, actual bore d = 0.260 m Straight length L = 45 m; fittings equivalent length = 15 m ν (seawater) = 1.05×10⁻⁶ m²/s f = 0.020 (from Moody chart)
Find the actual working velocity and the total friction head over the run
Check the minimum bore the velocity limit demands.
Rearranging the area–velocity relationship gives the smallest bore that keeps the design velocity at or below 2.5 m/s.
The next standard size above 226 mm is DN250 with an actual bore of 260 mm.
Rounding down would breach the velocity limit, so DN250 is the one to carry forward.
Find the actual velocity in the selected pipe.
A bore larger than the bare minimum means the true velocity sits below the 2.5 m/s ceiling.
Confirm the flow is turbulent before relying on the Moody-chart friction factor.
Fold the fittings into an equivalent length.
Run Darcy–Weisbach once against the total, so nothing is left uncounted.
AnswerV_act ≈ 1.88 m/s (within the 2.5 m/s limit); total friction head ≈ 0.83 m over the run.
The trap: sizing only to the bare minimum bore and then forgetting the fittings' equivalent length — on this run the fittings add a third again to the pipe's own straight length, enough to change the pump selection.
A bilge pump's centreline sits 3.0 m above the free surface of the source it draws from — a suction lift, not a flooded suction. The tank is open to atmosphere (101,325 Pa) and its contents have warmed to 40 °C, where the vapour pressure of water is 7,375 Pa. Friction and entry losses in the suction line up to the pump total 0.4 m. The pump manufacturer states NPSH required at the duty flow as 3.5 m. Find NPSH available and state whether the installation has an adequate margin.
Static suction lift h_s = 3.0 m (source below pump) Atmospheric pressure p_a = 101,325 Pa Water temperature = 40 °C; vapour pressure p_v = 7,375 Pa Suction line losses h_f = 0.4 m ρ = 1000 kg/m³, g = 9.81 m/s² NPSH required (from pump curve) = 3.5 m
Find NPSH available and state whether the installation has an adequate margin
Convert the atmospheric and vapour pressures to head.
So every term in the NPSH equation is in the same units.
Apply the sign correctly.
This is a suction lift — the source sits below the pump, so the static term works against the pump and must be subtracted, not added.
Compare with the pump's required figure to find the working margin.
AnswerNPSH_a ≈ 6.18 m against NPSH_r = 3.5 m — a margin of about 2.7 m, comfortably above the usual 0.5–1 m minimum.
The trap: treating this as a flooded suction and adding h_s instead of subtracting it — that single sign error overstates NPSH_a by twice the lift, here by 6.0 m, turning a genuinely marginal case into one that looks safe on paper; the 40 °C vapour-pressure term is just as easy to leave out entirely.
A jacket-water cooling pump running in a closed loop (no static lift — a pure friction circuit) has its duty point at 1450 rpm: flow 250 m³/h, head 32 m, absorbed shaft power 28 kW. A reduction in engine load means only 200 m³/h of cooling flow is now required. Because the loop is closed, the new duty point still lies on the same system parabola, so the affinity laws apply directly. Find the pump speed, head and absorbed power at the new duty point.
N₁ = 1450 rpm, Q₁ = 250 m³/h, H₁ = 32 m, P₁ = 28 kW Required new flow Q₂ = 200 m³/h Closed loop — system curve passes through the origin (no static head)
Find the pump speed, head and absorbed power at the new duty point
Find the flow ratio.
With no static head, the duty point at any speed lies on the same fixed parabola, so this one ratio drives all three affinity relationships together.
Speed scales directly with flow (Q∝N).
So the new running speed follows straight from the ratio.
Head scales with the square of the ratio (H∝N²).
Absorbed power scales with the cube of the ratio (P∝N³).
The term worth remembering, since it is what makes slowing the pump down worthwhile.
AnswerAt the new duty point: N₂ ≈ 1160 rpm, H₂ ≈ 20.5 m, P₂ ≈ 14.3 kW — roughly half the original power for 80% of the original flow.
The trap: reaching for these same three ratios to predict the effect of trimming the impeller diameter at constant speed instead of changing the speed — the diameter-trim relationships are only an approximation and unravel over larger cuts, so a trimmed-impeller duty point has to be read off the manufacturer's trimmed curve, not assumed from Q∝N, H∝N², P∝N³.
A = Q / Vrequired bore area for a chosen design velocityh_f = f·L·V²/(2gD)Darcy–Weisbach; f from Moody chart once turbulentf = 64/Re (laminar)Re < ~2000; use Moody chart above ~4000h_minor = K·V²/2gor convert each fitting to an equivalent length and add to LP_hyd = ρgQH, P_shaft = P_hyd/ηQ in m³/s; η always < 1NPSH_a = p_a/ρg ± h_s − h_f − p_v/ρg+h_s flooded suction, −h_s suction liftNPSH_a > NPSH_r + margincommonly ≥0.5–1 m; more for hot or volatile dutiesQ∝N, H∝N², P∝N³affinity laws — speed change only, not an impeller trimN_s = N√Q / H^(3/4)specific speed — selects impeller family (radial/mixed/axial)Design velocitysuction ≈1–2 m/s, discharge ≈2–3 m/s; tighter for seawater erosion